Voltage Drop Calculator

Calculate voltage drop from wire size, current, and distance

Frequently Asked Questions

Single-phase: VD = (2 × K × I × D) ÷ CM. Three-phase: VD = (1.732 × K × I × D) ÷ CM. Where K is the conductor material constant (12.9 for copper, 21.2 for aluminum, at 75°C), I is the current in amps, D is the one-way circuit distance in feet, and CM is the conductor's circular mil area (from NEC Chapter 9, Table 8).
The NEC recommends keeping voltage drop to 3% or less for branch circuits, and 5% total (combined feeder and branch circuit) for reasonable equipment efficiency — these are recommendations for good design, not hard code violations, but exceeding them can cause dimming, motor overheating, or reduced equipment lifespan.
Because the formula's factor (2 for single-phase, √3 for three-phase) already accounts for the round-trip current path — single-phase current must travel out and back (hence ×2), while three-phase's geometry uses the √3 factor instead. Enter only the one-way distance from source to load.
Use whichever matches your actual conductor material — copper (K=12.9) has meaningfully lower resistance than aluminum (K=21.2) of the same gauge, so an aluminum run needs a larger wire size to hit the same voltage drop target.

Voltage drop formula

Current flowing through a wire loses some voltage to the wire's resistance. The calculator uses the standard circular mil formula:

  • Single phase: VD = 2 × K × I × D ÷ CM
  • Three phase: VD = 1.732 × K × I × D ÷ CM

K is the resistance constant (12.9 ohm-cmil/ft for copper, 21.2 for aluminum), I is the load current in amps, D is the one-way length in feet, and CM is the conductor's area in circular mils. The factor of 2 covers the path out and back.

Example

A 120 V single-phase circuit carries 16 A to a load 100 feet away on 12 AWG copper (6,530 circular mils). The drop is 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.3 V, or 5.3%, too much for a branch circuit. Upsizing to 10 AWG (10,380 cmil) cuts it to 4.0 V (3.3%), and 8 AWG to 2.5 V (2.1%).

Recommended limits

Informational notes in the National Electrical Code suggest no more than 3% drop on a branch circuit and 5% total for the feeder and branch circuit together. These are recommendations for efficiency and equipment performance, not mandatory rules, although some local codes and equipment makers require them. Sensitive equipment, motors and LED drivers perform better with lower drop.

Circular mils for common wire sizes

SizeCircular mils
14 AWG4,110
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
2 AWG66,360
1/0 AWG105,600

Ways to reduce voltage drop

  • Use a larger wire size; doubling the circular mils halves the drop.
  • Run at a higher voltage, such as 240 V instead of 120 V, which halves the current for the same power.
  • Shorten the run or move the panel or subpanel closer to the load.

Voltage drop is separate from ampacity: the wire must also be rated for the current under NEC Table 310.16. For wattage and running costs, see the electricity cost calculator, and for lighting loads the lighting calculator.