Voltage Drop Calculator
Calculate voltage drop from wire size, current, and distance
Frequently Asked Questions
Voltage drop formula
Current flowing through a wire loses some voltage to the wire's resistance. The calculator uses the standard circular mil formula:
- Single phase: VD = 2 × K × I × D ÷ CM
- Three phase: VD = 1.732 × K × I × D ÷ CM
K is the resistance constant (12.9 ohm-cmil/ft for copper, 21.2 for aluminum), I is the load current in amps, D is the one-way length in feet, and CM is the conductor's area in circular mils. The factor of 2 covers the path out and back.
Example
A 120 V single-phase circuit carries 16 A to a load 100 feet away on 12 AWG copper (6,530 circular mils). The drop is 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.3 V, or 5.3%, too much for a branch circuit. Upsizing to 10 AWG (10,380 cmil) cuts it to 4.0 V (3.3%), and 8 AWG to 2.5 V (2.1%).
Recommended limits
Informational notes in the National Electrical Code suggest no more than 3% drop on a branch circuit and 5% total for the feeder and branch circuit together. These are recommendations for efficiency and equipment performance, not mandatory rules, although some local codes and equipment makers require them. Sensitive equipment, motors and LED drivers perform better with lower drop.
Circular mils for common wire sizes
| Size | Circular mils |
|---|---|
| 14 AWG | 4,110 |
| 12 AWG | 6,530 |
| 10 AWG | 10,380 |
| 8 AWG | 16,510 |
| 6 AWG | 26,240 |
| 4 AWG | 41,740 |
| 2 AWG | 66,360 |
| 1/0 AWG | 105,600 |
Ways to reduce voltage drop
- Use a larger wire size; doubling the circular mils halves the drop.
- Run at a higher voltage, such as 240 V instead of 120 V, which halves the current for the same power.
- Shorten the run or move the panel or subpanel closer to the load.
Voltage drop is separate from ampacity: the wire must also be rated for the current under NEC Table 310.16. For wattage and running costs, see the electricity cost calculator, and for lighting loads the lighting calculator.